Each entry has 89 settings. The seven of the Room step are the entry's data: change them with Reconfigure. The other 82 are its options: change them with Configure. Two are required: room_sensors and outdoor. A room also needs climate or heater_switch, and an AC needs power or ac_rated_w. See Set up the integration.
The Key column is the name in the config entry and in the diagnostics download. The label is the text on the form.
tests/ha/test_settings_effect.py runs each setting at two values over a scripted day. It fails when a setting stops changing the device commands or the published data.
The Home Assistant area of the room. Names a new entry and holds its device. Changes no device command.
climate
Air conditioner
unset
The AC that HVAC Horizon reads and, with control on, drives. Leave it empty for a room with heating only. A room needs this or heater_switch.
power
AC power sensor (W)
unset
Power of the whole AC unit in watts. Feeds the room model, the energy forecast and the running check: below 0.2 kW the AC counts as off. An AC needs this or ac_rated_w.
ac_rated_w
AC rated power (W)
unset
For an AC with no power sensor. The AC counts as drawing this while its hvac_action is cooling, heating or drying. An AC that reports no action counts by its mode.
heater_switch
Heater switch
unset
Switch for the heater plug. The heater output runs in 10 minute windows.
room_sensors
Room temperature sensors
required
One or more temperature sensors in the room. The room temperature is their median. A stalled sensor drops out of the median.
outdoor
Outdoor temperature sensor
required
Outdoor temperature. Feeds the room model, the forecast, the 16 °C cooling limit of the automatic mode with a window actuator or whole-house fan, and the 22 °C heating limit of the automatic mode and dry.
Its next_event attribute, an ISO time, sets the deadline for pre-cooling. When the room cannot reach the setpoint by the event and the event is within 120 minutes, cooling starts at once.
vacation
Vacation switch
unset
While on, cooling holds vacation_c and heating holds 16 °C.
vacation_c
Vacation temperature (°C)
27.0
Cooling target while vacation is on.
away_delay_min
Minutes before an empty house counts as away
30.0
Delay before an empty house counts as away.
comfort_c
Comfort temperature (°C)
24.0
The normal target. Range 16 to 30.
eco_c
Eco temperature (°C)
unset
Target for the eco preset. An unoccupied house cools to this value when set.
comfort_energy_weight
Comfort or savings (0 to 1)
unset
0 keeps the comfort target. 1 uses the eco setpoint. Needs eco_c.
heat_eco_c
Eco heating temperature (°C)
unset
Heat target for eco.
heat_boost_c
Boost heating temperature (°C)
unset
Heat target for boost.
boost_c
Boost temperature (°C)
23.0
Target for the boost preset.
away_c
Away temperature (°C)
27.0
Cooling target for an unoccupied house when eco_c is not set. Also the away preset target.
schedule_blocks
Schedule blocks (its own step)
[]
Presets by time of day. See [[guides/services-and-presets#schedule-blocks
Supplies the daily and hourly forecast. The day type, the night plan, the outdoor temperature series and the outdoor fallback use it. See Read the forecast.
heatwave_warning
Heatwave warning sensor
unset
A binary sensor. While it is on, the Heatwave sensor is on. It changes no device command.
cover
Blind or cover
unset
Closes the cover above 0.5 kW of solar gain. Opens it again below that.
window
Window or door sensor
unset
A window open longer than window_delay_min pauses cooling. The heater is also gated.
motion
Motion sensor in the room
unset
Motion in the room means occupied. No motion for motion_away_min means unoccupied: the room cools to eco_c or away_c and heats to the eco heat setpoint.
presence
Presence sources
unset
A source in state on or home means home. All sources away for away_delay_min means away. With a motion sensor, motion in the room counts as occupied whatever presence says. Once motion is idle, an empty house heats to the 16 °C frost floor.
window_actuator
Window opener
unset
Opens on natural ventilation or economizer advice. Closes when the advice ends. The AC does not cool while the entry holds the window open. When the room is still 2 K above the cool threshold after 30 minutes, the window closes and the AC cools. The same happens when the room is above the cool threshold and fell by less than 0.3 K in 30 minutes.
motion_away_min
Minutes without motion before the room is unused
30.0
Used only with motion. Minimum 1.
window_delay_min
Minutes a window may stay open
10.0
Minutes a window may stay open before cooling pauses. 0 to 120.
Keeps windows shut to humid air. Window advice, the economizer and the window actuator stay closed when the outdoor dew point is 1 K or more above the room's. With no room_humidity, the limit is an outdoor dew point of 20 °C.
room_humidity
Room humidity sensor
unset
Keeps room humidity between 40 % and the thermostat's humidity target (60 % by default). Above the target the dehumidifier runs. Below 40 % the humidifier runs. Sets the drying status.
co2
CO2 sensor
unset
Above 1000 ppm the room fan runs.
fan
Room fan switch
unset
Runs for ventilation.
dehumidifier
Dehumidifier switch
unset
On while room humidity is above the humidity target (60 % by default), off 3 points below it. In dry mode with no humidity sensor it stays on. Off while the room is held off.
humidifier
Humidifier switch
unset
On while room humidity is below 40 %, off at 43 %. Off while the room is held off.
pm25
PM2.5 sensor
unset
Above 25 µg/m³ the room fan runs.
whole_house_fan
Whole-house fan switch
unset
On when the room is above the cool threshold, outdoors is at least 2 K cooler and the house is not sealed. The AC stays off while the fan runs. When the room is still 2 K above the cool threshold after 30 minutes, the fan stops and the AC cools. The same happens when the room is above the cool threshold and fell by less than 0.3 K in 30 minutes.
coil_dry
Dry the AC coil after cooling
False
Runs the AC dry mode for 20 minutes after cooling.
dry_for_humidity
Dehumidify with the AC
False
Above the humidity target (60 % by default), with no dehumidifier set, the AC runs dry mode. Dry mode uses a lot of water.
economizer_fan
Help free cooling with the room fan
False
Runs the fan switch in the economizer fan assist phase. Needs home, unlocked and no stalled sensor.
auto_fan
Set the AC fan speed from the room
False
Sets the AC fan mode from the gap to the target while cooling.
Controller gains, output limits and timing. The defaults suit most rooms.
Key
Form label
Default
Effect
heater_kp
PID proportional gain
20.0
Used at the default. A value you set wins. At the default, the gain from a relay test applies.
heater_ki
PID integral gain (per hour)
60.0
Same rule as heater_kp.
heater_kd
PID derivative time (hours)
0.5
Same rule as heater_kp.
tpi_coef_int
TPI room coefficient
0.6
TPI gain on the room gap.
tpi_coef_ext
TPI outdoor coefficient
0.01
TPI gain on the outdoor gap.
tpi_threshold_high
TPI stop above target while rising (°C)
unset
With the low threshold, forces the TPI output to 0 while the room rises and is this far above the target. Both must be above 0 to apply. TPI then heats up to the larger threshold above the target.
tpi_threshold_low
TPI stop above target while falling (°C)
unset
With the high threshold, forces the TPI output to 0 while the room falls and is this far above the target. Both must be above 0 to apply.
max_on_percent
TPI maximum output (%)
unset
Caps the TPI output, 0 to 100 %.
output_min
Minimum heater output (%)
0.0
Lower limit for the heater output.
output_max
Maximum heater output (%)
100.0
Upper limit for the heater output.
output_min_entity
Minimum heater output from a number entity
unset
When set, its value overrides output_min.
output_max_entity
Maximum heater output from a number entity
unset
When set, its value overrides output_max.
min_on_min
Minimum AC on time (not used)
unset
Deprecated and ignored. A stop is never delayed.
min_off_min
Restart delay (minutes)
3.0
Restart delay. A start waits this long after the device stopped. 0 disables it. 0 to 120.
Lowers the setpoint sent to the AC by the gap between the room median and the AC's own current_temperature, so an AC whose sensor reads cool still runs. An AC with no such attribute is regulated from power.
fleet is a list of the heaters and coolers in the room. When it is set, HVAC Horizon picks which devices to run for the room's gap to the target. dispatch_mode sets the order: fast runs the device that delivers the most first, economy runs the device with the lowest cost per kelvin first. The dispatch sensor shows the choice. See Sensors.
The Room devices step adds one device per submit. Each device is stored with these keys.
Key
Required
Default
Meaning
device_id
required
none
Name of the device. Must be unique in the list.
kind
required
none
cool or heat.
rated_w
required
none
Watts the device draws while it runs. Used when there is no power sensor.
entity_id
optional
none
The climate entity that drives the device. A heat device can use a switch instead. Without it the device is chosen but not driven.
power_sensor
optional
none
Power sensor in watts. Its reading replaces rated_w while the device runs.
rate_k_per_h_per_kw
optional
none
Room change in kelvin per hour for each kW the device draws. A device without a rate is not chosen. Once the device has run alone for 6 intervals of 5 minutes, the fitted rate replaces it.