Use the room thermostat
Choose the mode, the target temperature and the preset on the room climate entity, and read what the devices are doing.
The room thermostat#
Each entry has one climate entity named HVAC Horizon <AC name>. Use it as the thermostat of the room. Leave the AC's own climate entity alone: HVAC Horizon sets its mode and setpoint.
The thermostat needs control on. With control off it reads off and its control attribute reads observe only. See Turn on control.
Modes#
The mode decides which devices may run. A device starts only when the room needs it.
| Mode | Cooling devices | Heating devices |
|---|---|---|
heat_cool | Run above the high target's threshold | Run below the low target's threshold |
auto | Run above the cool threshold | None in the room |
cool | Run above the cool threshold | Stay off |
heat | Stay off | Run below the heat threshold |
dry | The AC runs in its dry mode and does not cool | Run below the heat threshold |
fan_only | The AC runs its fan and does not cool | Stay off |
off | Stay off | Stay off |
The default is the automatic mode: the room runs whatever it needs. Its name follows Home Assistant's meaning of the two modes.
heat_coolin a room that can heat and cool. The card shows a low and a high target.autoin a room that only cools. The card shows one target.
Both are one behaviour, and the pages of this manual call it the automatic mode. A room with heating only has off and heat. Before 0.7.0 the automatic mode was named auto in every room. An automation that sets auto on a room that can heat must set heat_cool.
The thermostat lists heat when the entry can heat: a heater switch, ac_heat, mpc_heat_plan or a heating fleet device. It lists dry when the AC has a dry mode or the entry has a dehumidifier switch. It lists fan_only when the first AC has that mode and the room has no fleet devices.
Cooling devices are the AC, the second AC, cooling fleet devices, the whole-house fan and the window actuator. Heating devices are the heater switch, the AC in heat mode, the boiler, the valve and heating fleet devices.
The mode is stored. It is the same after a restart.
Off#
off sends off to every device of the entry in the same call. No minimum run time delays it. Nothing starts while the room is off, including after a restart of Home Assistant.
To leave off, choose a mode. The climate.turn_on action returns to the mode you had before off.
Dry#
In dry the AC runs in its own dry mode.
- With a room humidity sensor, the AC dries while the room is above the humidity target (60 % by default) and goes off 3 points below it.
- With no room humidity sensor, the AC dries until you change the mode.
- An entry with a dehumidifier switch runs that switch and leaves the AC off.
Drying cools the room. The heater may run at the same time to hold the heat target. In dry the heater obeys the outdoor heating limit, so it stays off when outdoors is above 22 °C. When the room falls 1 K below the heat threshold, the AC pauses. It dries again once the room is back at the threshold.
Fan#
In fan_only the first AC runs in its own fan mode. Nothing cools and nothing heats, at any room temperature. The fan starts with no restart delay, because no compressor starts. A stalled room sensor turns the AC off.
Restart delay#
A start after a stop waits for the restart delay, 3 minutes by default. The thermostat shows the wait in its pending attribute:
start in 3 min: restart delayThe device starts by itself when the delay ends. Set the delay with min_off_min in the Expert tuning section. 0 turns it off.
Outdoor limits#
An entry with a window actuator or a whole-house fan cools with outdoor air first. In the automatic mode its AC stays off while outdoors is below 16 °C. The limit ends when the open window or the fan has left the room 2 K above the cool threshold for 30 minutes, or cooled it by less than 0.3 K in 30 minutes. An entry with neither has no outdoor cooling limit. cool has no outdoor limit: the AC cools whenever the room is above the cool threshold.
In the automatic mode the AC does not cool while the heater runs or within 60 minutes of its last run. A room 2 K above the cool threshold cools at once. This stops the heater and the AC from taking turns.
In the automatic mode and dry the heater stays off while outdoors is above 22 °C. heat has no outdoor limit: the heater runs whenever the room is below the heat threshold.
When the room is below the heat threshold and a gate holds the heater off, pending names the gate:
pending | Cause |
|---|---|
heat held: outdoors above 22 °C | The mode is automatic or dry and outdoors is above 22 °C. |
heat held: window open | The window sensor reads open. |
heat held: house mode is away | The house mode is away. |
heat held: another room is cooling | Another entry of the same house cools. |
heat held: locked | The lock is on. |
heat held: a sensor has stalled | A room or outdoor sensor has stopped reporting. |
Target temperature#
The target is the comfort temperature, 16 to 32 °C in steps of 0.5. Setting it stores your value, and HVAC Horizon keeps it across restarts.
A target you set applies at once. The room returns to the comfort preset: a timed preset ends, and a schedule block with another preset is set aside until the schedule moves to its next block. Two states still override it: the vacation switch, and an away house or an empty room.
The thermostat shows the target you set, with these exceptions:
- A preset other than
comfortshows its own setpoint. - While the vacation switch is on, it shows
vacation_c. - In
heatmode it shows the heat target. Incool,dry,fan_onlyandoffit shows the cool target. - In the automatic mode, a room that can heat shows two targets. See below.
The threshold the AC cools above can sit above the cool target. A high price raises it by up to 1 K, and the comfort-versus-energy weight and the mould bump raise it too. A low price does not lower it. The Cool above sensor shows the threshold. See Actions and presets.
The AC cools when the room is above the cool threshold. The heater heats when the room is 0.5 K or more below the heat target. The sensors Cool above and Heat below show both values.
Low and high target in auto#
In the automatic mode, a room that can heat shows a low and a high target. The room heats to the low target and cools above the high one. Set both on the card, or with climate.set_temperature and target_temp_low and target_temp_high. The low target must not be above the high target.
Setting one temperature, in any mode, sets both targets to it. cool mode shows the high target and heat mode the low one.
Fan mode, swing mode and humidity#
The card lists the fan modes and swing modes of the first AC, when the AC has them. A change goes to that AC at once. With auto_fan on, the integration sets the fan mode again on its next tick.
With a room humidity sensor set, the card shows the room humidity.
Humidity target#
The card has a humidity target when the entry has a room humidity sensor and a device that dries: a dehumidifier switch or an AC with a dry mode. Set it on the card or with climate.set_humidity. The range is 35 to 75 % and the default is 60 %. The target is stored.
| Device | When it runs |
|---|---|
| Dehumidifier switch | Above the target, in every mode. Off 3 points below it. |
| AC dry mode | Above the target, in dry mode or with dry_for_humidity on. Off 3 points below it. |
| Humidifier switch | Below 40 %, or below the target minus 20 when the target is under 60 %. |
Presets#
| Preset | Cools above | Heats to |
|---|---|---|
comfort | Your target | Your target |
eco | eco_c, or your target when unset | heat_eco_c, or your target minus 1 |
boost | boost_c (23 °C) | heat_boost_c, or your target plus 1 |
away | away_c (27 °C) | 16 °C |
A preset you choose holds until the schedule moves to another block. It is not kept across a restart. See Actions and presets for schedule blocks and timed presets.
Action#
The hvac_action attribute shows what the devices do now.
| Action | Meaning |
|---|---|
cooling | The AC is in cool mode and draws 0.2 kW or more, or a cooling fleet device runs |
heating | The heater switch is on, the AC heats, or a heating fleet device runs |
drying | The AC is in dry mode and draws 0.2 kW or more, or the dehumidifier runs in dry mode |
fan | The AC is in its fan mode and nothing heats or cools |
idle | Nothing runs, or the AC is in cool, heat or dry mode and draws under 0.2 kW |
off | The room is held off |
The action follows the devices as they change. The mode is your choice and does not change when a device starts or stops.
Errors#
| Message | Cause | Fix |
|---|---|---|
HVAC Horizon entry is locked | The lock is on, so the target, the preset and the mode cannot change. | Unlock with hvac_horizon.set_lock. See [[guides/services-and-presets#lock-and-pin |