Troubleshoot
Find out why the AC or the heater is on or off, what each action text means, and how to clear each repair issue.
Find the reason#
HVAC Horizon writes one action text on each tick. Read it in two places:
- The Daily briefing sensor, after
Next:. - The
investigationattribute of the Status sensor, with the recent actions.
Then find the text in the table below.
Action texts#
| Text | Cause | What to do |
|---|---|---|
cool: above comfort target | The room is above the cool threshold. The preset name replaces comfort under another preset. | Nothing. |
off: at or below comfort target | The room needs no cooling. | Nothing. |
off: user turned the room off | The room thermostat is off. | Choose a mode. |
off: mode is heat: no cooling | The room is above the cool threshold and the thermostat is in heat or dry. The text names the mode. | Choose cool or the automatic mode. |
fan: the AC runs its fan only | The thermostat is in fan_only. | Choose another mode to cool or heat. |
cool: waiting for restart delay | A start waits for min_off_min after the last stop. The same text exists for heat and dry. | Wait. The pending attribute of the thermostat shows the minutes. |
cool: waiting for compressor group | Another entry in the same compressor_group started its AC less than 5 minutes ago. | Wait. |
off: window open N min | The window sensor has been open for window_delay_min or longer. | Close the window. |
off: free cooling: window open or whole-house fan | The entry holds the window actuator open, or the whole-house fan runs. | Nothing. The AC cools when the room is still 2 K above the cool threshold after 30 minutes, or fell by less than 0.3 K in 30 minutes. |
off: auto: the heater ran in the last 60 min | The mode is automatic and the heater runs, or stopped less than 60 minutes ago. | Nothing. A room 2 K above the cool threshold cools at once. Choose cool to cool now. |
off: outdoor N C below cooling limit | The mode is automatic, the entry has a window actuator or a whole-house fan, and outdoors is below 16 °C. | Nothing. The window or the fan cools the room. Choose cool to run the AC. |
off: away, room within setback | The room is unoccupied and below eco_c or away_c. | Nothing. |
cool: pre-cool starts now | A schedule event is near and the room needs the time to cool. | Nothing. |
off: dry paused, room below heat threshold | Dry mode cooled the room to 1 K below the heat threshold. | Nothing. Drying resumes at the threshold. |
off: night hold: AC does not start | night_plan_act is on and the night plan is hold. | Turn night_plan_act off to cool. |
off: sensor stalled | A sensor stall blocks the AC. | See Sensor stalled. |
off: no room reading | No room sensor has had a valid reading for the stall window. | Check the room sensors. |
inhibited after a manual change | Someone changed the AC setpoint by hand, or turned the AC off at the unit, in the last 30 minutes. | See Manual changes. |
locked | The lock is on. | Unlock with hvac_horizon.set_lock. |
locked: off, sensor stalled | The lock is on and a safety stop turned the AC off. The reason can also be window open or house away. | Clear the cause, or unlock. |
The AC does not start#
Check these in order.
- Control. The thermostat reads
offand itscontrolattribute readsobserve onlywhile control is off. See Turn on control. - Mode. The AC cools in the automatic mode and
coolonly. - Threshold. The AC cools when the room is above the Cool above sensor. A room 0.5 K or less above it does not start the AC.
- Restart delay. The
pendingattribute readsstart in N min: restart delay. - The AC's own sensor. An AC whose built-in sensor reads cooler than the room may not run its compressor at the room's target.
setpoint_regulationsends a lower setpoint to make up the gap. The sensors Setpoint sent and Sensor offset show the values.
The heater does not start#
- Mode. The heater runs in the automatic mode,
heatanddryonly. It stays off incoolandfan_only. - Outdoor limit. In the automatic mode and
drythe heater stays off while outdoors is above 22 °C, and the Heating allowed binary sensor is off. Chooseheatto heat on a warm day. - Threshold. The heater runs when the room is below the Heat below sensor.
- AC cooling. The heater stays off on a tick where the AC cools, and while another entry of the same house cools.
- Window and house. An open window, an away house, vacation and the lock each hold the heater at 0.
When the room is below the heat threshold and one of these holds the heater, the pending attribute of the thermostat names it, for example heat held: outdoors above 22 °C.
Sensor stalled#
A sensor is stalled when its last report is older than the stall window, 900 seconds by default. Set the window with stall_window_s in Expert tuning, 300 to 3600 seconds. A sensor that repeats the same value still reports, so a steady reading is not a stall. unavailable and unknown count as no reading.
| Condition | AC and room devices | Heater |
|---|---|---|
| The outdoor sensor is stalled and no hourly forecast under 2 hours old exists | Off | 0 % |
| The outdoor sensor is stalled and a fresh hourly forecast exists | Run on the forecast temperature | Runs on the forecast temperature |
| Every room sensor is stalled | Off | 0 % |
| One room sensor is stalled and another is fresh | Run on the fresh sensors | Unchanged |
A stall also keeps the window actuator and the whole-house fan from starting. HVAC Horizon raises the repair issue HVAC Horizon sensors not updating with the list of sensors. The issue clears when they report again.
The AC is on and the compressor does not run#
The AC failure binary sensor turns on, and a repair issue and a notification appear, when all of these hold:
- The entry has a power sensor.
- The first AC has been in
coolordryfor 20 minutes or longer. - The room still needs it for that whole time. For
coolthe room is more than 0.5 K above the Cool above sensor. Fordrythe room humidity is at or above the humidity target. - The power was under 200 W for more than half of the last 20 minutes.
Check the unit for an error code. On a portable unit, check whether the water tank is full: such a unit keeps reporting its mode while the compressor rests.
The sensor turns off when the compressor has run for 15 of the last 20 minutes, when the AC leaves the mode, or when the room no longer needs it.
Two cases get no check: dry mode in a room with no humidity sensor, and the 20 minute coil dry after cooling.
A unit that rests its compressor for more than half the time in dry mode by design raises the issue while the humidity is above the target. Ignore the repair issue and disable the binary sensor for such a unit.
To get the alert on a phone, add an automation on the binary sensor:
triggers:
- trigger: state
entity_id: binary_sensor.hvac_horizon_bedroom_ac_failure
to: "on"
actions:
- action: notify.mobile_app_phone
data:
message: The AC is on and its compressor is not running. Check the water tank.Manual changes#
When the AC setpoint differs from the value HVAC Horizon last wrote by more than 0.05 K, HVAC Horizon treats it as your change. It sends no commands for 30 minutes. Each new change starts a new 30 minutes.
Turning the AC off at the unit, with its remote or on its own entity starts the same 30 minutes. This applies to the first AC, once it has reported the mode HVAC Horizon set. After the 30 minutes the AC starts again when the room still needs it. An AC that you turn on again in the same mode within the 30 minutes keeps running, and HVAC Horizon takes that mode as the one it set. After any other mode change at the unit, HVAC Horizon sets its own mode again and raises HVAC Horizon mode does not match.
Four commands still go out in that time: a stall stop, every heater turn-off, a window close, and off from the room thermostat.
To change the room without the 30 minute pause, use the room thermostat.
Off and restarts#
- Off from the room thermostat goes to every device in the same call.
- A room that is
offwhen Home Assistant starts sends no start command on any tick. - No device starts before the first valid room and outdoor readings arrive.
- When an entry is removed or control is turned off, HVAC Horizon turns off the outputs it commanded.
Repair issues#
Each issue clears when its cause ends. None has a fix flow.
| Issue | Raised when | Check |
|---|---|---|
HVAC Horizon sensors not updating | A room or outdoor sensor is stalled. | The sensors listed in the issue. |
HVAC Horizon heater is not warming the room | The heater ran 60 minutes and the room rose less than 0.5 K. | The heater, its plug and its switch. |
HVAC Horizon AC is not running its compressor | The AC has been in cool or dry for 20 minutes with demand and its power stayed under 200 W for more than half of them. | The unit's error code, and the water tank of a portable unit. |
HVAC Horizon mode does not match | The AC mode differs from the last mode written and the setpoint did not change. | The AC unit, and any other automation that sets its mode. |
Send a bug report#
Open the entry, select the three-dot menu and Download diagnostics. The file holds the settings, the room model and the last result, with entity IDs redacted. Attach it to an issue at github.com/belikh/hvac-horizon.
A device does not follow a command#
The Unconfirmed commands sensor lists each device whose state differs from the last command on two ticks in a row, as switch.heater: expected on, is off. A command that the device refused is listed on the next tick, as climate.ac: climate.set_hvac_mode failed: and the reason. The log has one warning for each device.
A device that fails does not hold up the others. The tick goes on to the next device, and the safety stop turns every other output off.
| Cause | Fix |
|---|---|
| The device is offline or its integration lost the connection. | Restore the device. Each tick sends the command again. |
| Someone changed the device by hand. | Nothing. The entry is listed until the states agree. |
| A relay is stuck. | Replace it. HVAC Horizon reports it and cannot open it. |
The watchdog turned the outputs off#
A timer separate from the control tick checks every minute when the last tick finished. After 16 minutes with no finished tick it runs one tick itself. When that tick fails too, the next check turns off the heater, the AC, the second AC, the fleet devices and every switch the entry turned on. The log has No control tick has finished for N s. The Watchdog trips sensor counts these. Control resumes at the next tick that finishes.
A trip means every tick raised an error for 16 minutes, or one tick never returned. Download the diagnostics and the log and open an issue.