Troubleshoot

Find out why the AC or the heater is on or off, what each action text means, and how to clear each repair issue.

Find the reason#

HVAC Horizon writes one action text on each tick. Read it in two places:

  • The Daily briefing sensor, after Next:.
  • The investigation attribute of the Status sensor, with the recent actions.

Then find the text in the table below.

Action texts#

The AC does not start#

Check these in order.

  1. Control. The thermostat reads off and its control attribute reads observe only while control is off. See Turn on control.
  2. Mode. The AC cools in the automatic mode and cool only.
  3. Threshold. The AC cools when the room is above the Cool above sensor. A room 0.5 K or less above it does not start the AC.
  4. Restart delay. The pending attribute reads start in N min: restart delay.
  5. The AC's own sensor. An AC whose built-in sensor reads cooler than the room may not run its compressor at the room's target. setpoint_regulation sends a lower setpoint to make up the gap. The sensors Setpoint sent and Sensor offset show the values.

The heater does not start#

  1. Mode. The heater runs in the automatic mode, heat and dry only. It stays off in cool and fan_only.
  2. Outdoor limit. In the automatic mode and dry the heater stays off while outdoors is above 22 °C, and the Heating allowed binary sensor is off. Choose heat to heat on a warm day.
  3. Threshold. The heater runs when the room is below the Heat below sensor.
  4. AC cooling. The heater stays off on a tick where the AC cools, and while another entry of the same house cools.
  5. Window and house. An open window, an away house, vacation and the lock each hold the heater at 0.

When the room is below the heat threshold and one of these holds the heater, the pending attribute of the thermostat names it, for example heat held: outdoors above 22 °C.

Sensor stalled#

A sensor is stalled when its last report is older than the stall window, 900 seconds by default. Set the window with stall_window_s in Expert tuning, 300 to 3600 seconds. A sensor that repeats the same value still reports, so a steady reading is not a stall. unavailable and unknown count as no reading.

A stall also keeps the window actuator and the whole-house fan from starting. HVAC Horizon raises the repair issue HVAC Horizon sensors not updating with the list of sensors. The issue clears when they report again.

The AC is on and the compressor does not run#

The AC failure binary sensor turns on, and a repair issue and a notification appear, when all of these hold:

  • The entry has a power sensor.
  • The first AC has been in cool or dry for 20 minutes or longer.
  • The room still needs it for that whole time. For cool the room is more than 0.5 K above the Cool above sensor. For dry the room humidity is at or above the humidity target.
  • The power was under 200 W for more than half of the last 20 minutes.

Check the unit for an error code. On a portable unit, check whether the water tank is full: such a unit keeps reporting its mode while the compressor rests.

The sensor turns off when the compressor has run for 15 of the last 20 minutes, when the AC leaves the mode, or when the room no longer needs it.

Two cases get no check: dry mode in a room with no humidity sensor, and the 20 minute coil dry after cooling.

A unit that rests its compressor for more than half the time in dry mode by design raises the issue while the humidity is above the target. Ignore the repair issue and disable the binary sensor for such a unit.

To get the alert on a phone, add an automation on the binary sensor:

Manual changes#

When the AC setpoint differs from the value HVAC Horizon last wrote by more than 0.05 K, HVAC Horizon treats it as your change. It sends no commands for 30 minutes. Each new change starts a new 30 minutes.

Turning the AC off at the unit, with its remote or on its own entity starts the same 30 minutes. This applies to the first AC, once it has reported the mode HVAC Horizon set. After the 30 minutes the AC starts again when the room still needs it. An AC that you turn on again in the same mode within the 30 minutes keeps running, and HVAC Horizon takes that mode as the one it set. After any other mode change at the unit, HVAC Horizon sets its own mode again and raises HVAC Horizon mode does not match.

Four commands still go out in that time: a stall stop, every heater turn-off, a window close, and off from the room thermostat.

To change the room without the 30 minute pause, use the room thermostat.

Off and restarts#

  • Off from the room thermostat goes to every device in the same call.
  • A room that is off when Home Assistant starts sends no start command on any tick.
  • No device starts before the first valid room and outdoor readings arrive.
  • When an entry is removed or control is turned off, HVAC Horizon turns off the outputs it commanded.

Repair issues#

Each issue clears when its cause ends. None has a fix flow.

Send a bug report#

Open the entry, select the three-dot menu and Download diagnostics. The file holds the settings, the room model and the last result, with entity IDs redacted. Attach it to an issue at github.com/belikh/hvac-horizon.

A device does not follow a command#

The Unconfirmed commands sensor lists each device whose state differs from the last command on two ticks in a row, as switch.heater: expected on, is off. A command that the device refused is listed on the next tick, as climate.ac: climate.set_hvac_mode failed: and the reason. The log has one warning for each device.

A device that fails does not hold up the others. The tick goes on to the next device, and the safety stop turns every other output off.

The watchdog turned the outputs off#

A timer separate from the control tick checks every minute when the last tick finished. After 16 minutes with no finished tick it runs one tick itself. When that tick fails too, the next check turns off the heater, the AC, the second AC, the fleet devices and every switch the entry turned on. The log has No control tick has finished for N s. The Watchdog trips sensor counts these. Control resumes at the next tick that finishes.

A trip means every tick raised an error for 16 minutes, or one tick never returned. Download the diagnostics and the log and open an issue.