Actions and presets

Set presets by schedule or timer, and call the HVAC Horizon actions for the lock, house mode, auto-tune, export and what-if.

Which preset applies#

A preset sets the cool threshold and the heat target. HVAC Horizon uses the first of these that applies:

  1. A timed preset, while its minutes run. See start_timed_preset below.
  2. The preset you chose on the room thermostat, until the schedule moves to another block.
  3. The schedule block that covers the current local hour.
  4. comfort.

Three things move these values:

  • Price. With a price sensor, the cool threshold rises above the midpoint of the cheap and the expensive price, up to 1 K at the expensive price. A low price leaves it at your target.
  • Boost with a heater. When heating is allowed, boost lifts its cool threshold to the heat target plus 0.5 K. The AC then does not cool while the heater heats.
  • Vacation. While the vacation switch is on, vacation_c replaces the comfort target and heating holds 16 °C.

Schedule blocks#

Open Configure and select Schedule blocks. A block applies a preset between two times of day.

  1. Set New block starts at and New block ends at.
  2. Choose the preset: comfort, eco, boost or away.
  3. Select Submit. Turn on Add another block after this one first to stay on the form.

To remove blocks, tick them under Remove these blocks and select Submit.

A block whose end is before its start runs past midnight. Times outside every block use comfort. Two blocks cannot share a time of day: the form refuses a new block that overlaps one you have. The entry stores the blocks as schedule_blocks, a list of start_h, end_h and preset, which the diagnostics download shows.

Before a comfort block, the heater starts early when the learned heat-up time needs it. The Heat-up time sensor shows the estimate in minutes.

Run a preset for a set time#

minutes is 1 to 720. When the time ends, the schedule preset applies again. Find the entry_id in the URL of the entry's page, or in its diagnostics download.

Actions#

The actions exist as soon as the integration is installed. An action on an entry that is not loaded fails with the HVAC Horizon entry <title> is not loaded. A value an action refuses, such as a setpoint out of range, shows its reason in Home Assistant.

Every action except set_house_mode takes entry_id. The actions marked response only return data and change nothing. The actions marked admin need an administrator: a call from another user fails with Unauthorized.

what_if accepts 0 to 50 °C for room_c and target_c, -20 to 60 °C for outdoor_c, and 0 to 10 kW for power_kw.

Lock and PIN#

The lock stops normal commands, so nobody changes the room by accident.

  1. Open Configure, select Advanced and enter a value in Lock PIN. Select Submit, then Save and close.
  2. Call hvac_horizon.set_lock with locked: true.
  3. To unlock, call it with locked: false and pin set to the PIN.

set_lock needs an administrator, to lock and to unlock.

While locked, HVAC Horizon sends no AC setpoint, valve, cover or window command, and holds the heater output at 0. The room thermostat refuses a new target, preset or mode. A stalled sensor, a window open longer than window_delay_min or an away house still turns the AC and the room devices off. The lock is stored and stays on after a restart.

Auto-tune the heater#

start_autotune switches the heater on and off around a setpoint and derives PID gains from the room's swing.

The setpoint is 15 to 26 °C and at least 2 K above the room. The test ends after 120 minutes, when the AC cools, or when the room reaches the heat threshold. The Status sensor's autotune_status attribute reads running, done, timed_out, cancelled or reached_cutoff. The gains apply to any of heater_kp, heater_ki and heater_kd that you left at its default.

House mode#

set_house_mode stores the mode with each entry. It survives a restart. The default is home.